SPS 321.03(7)(a)1.1. At least one exit door shall be a swing-type door at least 80 inches high by 36 inches wide.
SPS 321.03(7)(a)2.2. Except as allowed under subds. 3. and 4., other required exit doors shall be at least 76 inches high by 32 inches wide.
SPS 321.03(7)(a)3.3. Where double doors are used as a required exit, each door leaf shall provide a clear opening at least 30 inches wide and be at least 76 inches high.
SPS 321.03(7)(a)4.4. Where sliding doors are used as a required exit, the clear opening shall be at least 29 inches wide and be at least 76 inches high.
SPS 321.03(7)(b)(b) All exit doors shall be openable from the interior without the use of a key.
SPS 321.03(8)(8)Balconies.
SPS 321.03(8)(a)(a) Balconies shall be made of concrete, metal or wood which is treated, protected or naturally decay-resistive in accordance with s. SPS 321.10.
SPS 321.03(8)(b)(b) Balconies shall be provided with guards in accordance with s. SPS 321.04 (3).
SPS 321.03(8)(c)(c) Balconies which are required for exit purposes shall also comply with all of the following requirements:
SPS 321.03(8)(c)1.1. The balcony guard shall terminate no more than 46 inches above the floor level of the balcony.
SPS 321.03(8)(c)2.2. The floor level of the balcony shall be no more than 15 feet above the grade below.
SPS 321.03(8)(c)3.3. The floor of the balcony shall have minimum dimensions of 3 feet by 3 feet. The guard and its supports may infringe on the dimensions of the required area no more than 4.5 inches.
SPS 321.03(9)(9)Split level dwellings. In determining the exit requirement in a split level dwelling, all levels that are to be considered a single story shall be within 5 feet of each other.
SPS 321.03(10)(10)Two-family dwellings. In a 2-family dwelling, each dwelling unit shall be provided with exits in compliance with this section.
SPS 321.03(11)(11)Exits to courtyards. No exit may discharge to a courtyard having a perimeter that is entirely enclosed by exterior building walls or other obstructions that prevent pedestrian passage.
SPS 321.03 HistoryHistory: Cr. Register, November, 1979, No. 287, eff. 6-1-80; r. and recr. Register, February, 1985, No. 350, eff. 3-1-85; emerg. am. (1) (b), (2) and (5) (b) 2., eff. 5-7-85; r. (1) (b), renum. (1) (a) to be (1), am. (2), (7) and (8), r. and recr. (5) to (6), cr. (6m) and (10) to (12), Register, January, 1989, No. 397, eff. 2-1-89; am. (3) and (7), r. and recr. (10) and (11), Register, March, 1992, No. 435, eff. 4-1-92; am. (8), r. and recr. (10) (a), Register, November, 1995, No. 479, eff. 12-1-95; am. (6m) (b) 1. and 2., r. (6m) (b) 3., Register, January, 1999, No. 517, eff. 2-1-99; r. and recr. (1), (5), (7) and (8), am. (2) (b), r. (6), renum. (6m) to be (6) and r. and recr. (6) (d) and (e) as renum., Register, March, 2001, No. 543, eff. 4-1-01; reprinted to correct printing error in (6) (e) 2., Register September 2001 No. 549; CR 02-077: am. (1) (a), (5) (a) (intro.) and (10) (b), r. and recr. (1) (e), cr. (1) (f) to (h), Register May 2003 No. 569, eff. 8-1-03; CR 03-097: am. (1) (h) 1., Register November 2004 No. 587, eff. 1-1-05; CR 08-043: am. (title) and (1) (b), r. and recr. (3) and (7), renum. (6) (e) 5. and (10) to (12) to be (6) (e) 5. a. and (8) to (10), cr. (6) (e) 5. b. to d., r. (8) and (9) Register March 2009 No. 639, eff. 4-1-09; correction in (2) (a) made under s. 13.92 (4) (b) 7., Stats., Register March 2009 No. 639; CR 09-104: am. (1) (c) Register December 2010 No. 660, eff. 1-1-11; correction in (6) (d) 5., (e) 4., (8) (a), (b) made under s. 13.92 (4) (b) 7., Stats., Register December 2011 No. 672; CR 15-041: am. (1) (c), (d), cr. (1) (h) 3., am. (2) (a) to (c), (6) (d) 5., (e) 4., 5. a., cr. (6) (f), am. (7) (a) 4., (8) (b), (c) 1., 3., cr. (11) Register December 2015 No. 720, eff. 1-1-16.
SPS 321.035SPS 321.035Interior circulation.
SPS 321.035(1)(1)Doors and openings. All doors and openings to the following areas shall be at least 80 inches high and provide either a net clear opening width of 30 inches or be a 32-inch door:
SPS 321.035(1)(a)(a) Except as provided under pars. (b) and (c), all entrances into common use areas.
SPS 321.035(1)(b)(b) At least 50% of the bedrooms.
SPS 321.035(1)(c)1.1. At least one full bathroom, including doors or openings to a sink, toilet and tub or shower. If this bathroom is accessible only through a bedroom, the bedroom door shall meet the minimum width requirements of this section.
SPS 321.035(1)(c)2.2. If one or more full bathrooms are provided on the first floor, the bathroom meeting the requirements under this section shall be on the first floor.
SPS 321.035 NoteNote: This section does not require a full bathroom on the first floor.
SPS 321.035(2)(2)Hallways.
SPS 321.035(2)(a)(a) Except as allowed under par. (b), the clear width of hallways shall be at least 36 inches.
SPS 321.035(2)(b)(b) The following are allowed to infringe on the required clear width of a hallway:
SPS 321.035(2)(b)1.1. Door hardware and finish trim.
SPS 321.035(2)(b)2.2. Handrails may infringe into the minimum width of a hallway up to 4½ inches on each side.
SPS 321.035(2)(b)3.3. Heating registers may infringe into the minimum width of a hallway up to 4½ inches and no part of the register may be more than 38 inches above the floor.
SPS 321.035(2)(b)4.4. Ducts, pipes, light fixtures, structural features, and corner treatments that are within 84 inches of the floor may infringe into the minimum width of a hallway by a maximum of 4½ inches on each side.
SPS 321.035(2)(b)5.5. Unlimited infringements are allowed in a hallway more than 84 inches above the floor.
SPS 321.035(3)(3)Kitchens.
SPS 321.035(3)(a)(a) There shall be at least 30 inches of clearance between a wall, a permanently-installed kitchen island, permanently-installed kitchen cabinets and the following kitchen appliances, if provided:
SPS 321.035(3)(a)1.1. A range, cook top or oven.
SPS 321.035(3)(a)2.2. A sink, refrigerator or freezer.
SPS 321.035(3)(b)(b) Measurements shall be taken from the face of the wall, island, cabinet or appliance, ignoring knobs and handles.
SPS 321.035 NoteNote: See ICC/ANSI A117.1 chapter 10 for more guidelines relating to doors and accessible routes. Under that standard, doors must be at least 80-inches in height and provide a minimum net clear opening of 31¾-inches in width in order to provide accessibility for people with disabilities.
SPS 321.035 HistoryHistory: CR 08-043: cr. Register March 2009 No. 639, eff. 4-1-09.
SPS 321.04SPS 321.04Stairways and elevated areas.
SPS 321.04(1)(1)Scope.
SPS 321.04(1)(a)(a) General. Except as provided under par. (b), the following stairways shall conform to the requirements of this section.
SPS 321.04(1)(a)1.1. Every interior and exterior stairway attached to, or supported by any part of the structure covered under this code.
SPS 321.04(1)(a)2.2. Tub access stairs, unless they are an integral part of an approved plumbing product.
SPS 321.04(1)(b)(b) Exceptions. The following stairways are not required to comply with the requirements of this section:
SPS 321.04(1)(b)1.1. Stairways leading to non-habitable attics or crawl spaces.
SPS 321.04(1)(b)2.2. Non-required stairways connecting the basement directly to the exterior of the structure without communicating with any other part of the structure.
SPS 321.04(2)(2)Details.
SPS 321.04(2)(a)(a) Width.
SPS 321.04(2)(a)1.1. Except for spiral staircases under subd. 2., stairways shall measure at least 36 inches in width. Handrails and associated trim may project a maximum of 4.5 inches into the required width at each side of the stairway. The minimum clear width at and below the handrail, including at treads and landings, may not be less than 31.5 inches where a handrail is installed on one side, and 27 inches where handrails are provided on both sides.
SPS 321.04(2)(a)2.2. Spiral staircases shall be at least 26 inches wide measured from the outer edge of the supporting column to the inner edge of the handrail.
SPS 321.04(2)(b)(b) Riser height.
SPS 321.04(2)(b)1.a.a. Except for spiral staircases under subd. 2., risers may not exceed 8 inches in height measured vertically from tread to tread.
SPS 321.04(2)(b)1.b.b. At the top and bottom of a flight, measurement shall be taken from the top of the nosing to the finished floor surface unless the finished surface is carpeting, in which case measurement shall be made to the hard surface below the carpeting.
SPS 321.04(2)(b)2.2. Risers in spiral staircases may not exceed 9.5 inches in height measured vertically from tread to tread.
SPS 321.04(2)(c)(c) Tread depth.
SPS 321.04(2)(c)1.1. ‘Rectangular treads.’ Rectangular treads shall have minimum tread depth of 9 inches measured horizontally from nosing to nosing.
SPS 321.04(2)(c)2.2. ‘Spiral staircase treads.’ Spiral staircase treads shall have a minimum tread depth of 7 inches from nosing to nosing measured at a point 12 inches from the outer edge of the center column.
SPS 321.04(2)(c)3.3. ‘Winder treads in series.’ Two or more winder treads may be placed immediately adjacent to each other anywhere in a stairway provided both of the following conditions are met:
SPS 321.04(2)(c)3.a.a. The winder treads shall have a minimum tread depth of 7 inches measured at a point 12 inches from the narrow end of the tread.
SPS 321.04(2)(c)3.b.b. The depth of the immediately adjoining winder treads shall be equal at a point 12 inches from the narrow end of the tread or inside face of spindles or balusters.
SPS 321.04(2)(c)3.c.c. Winder treads may not be used on a straight stairway.
SPS 321.04(2)(c)4.4. ‘Individual winder treads.’
SPS 321.04(2)(c)4.a.a. An individual winder tread may be placed between rectangular treads or at the end of a flight of rectangular treads provided the tread depth is at least 9 inches, when measured at a distance of 12 inches from the narrow end of the tread or from the inside face of the wall.
SPS 321.04(2)(c)4.b.b. There may be more than one individual winder tread in a stairway.
SPS 321.04(2)(c)4.c.c. Winder treads may not be used on a straight stairway.
SPS 321.04(2)(d)(d) Headroom.
SPS 321.04(2)(d)1.1. Stairways shall be provided with a minimum headroom clearance of 76 inches measured vertically from a line parallel to the nosing of the treads to the ceiling, soffit or any overhead obstruction directly above that line.
SPS 321.04(2)(d)2.2. The headroom clearance shall be maintained over an intermediate landing.
SPS 321.04(2)(d)3.3. The headroom clearance shall be maintained over a landing that is at the top or bottom of a stairway for a minimum distance of 36 inches in the direction of travel of the stairway.
SPS 321.04(2)(e)(e) Uniformity.
SPS 321.04(2)(e)1.1. Within a stairway flight, the greatest tread depth may not exceed the smallest tread depth by more than 3/8 inch and the greatest riser height may not exceed the smallest riser height by more than 3/8 inch.
SPS 321.04(2)(e)2.2. The allowed variation in uniformity under subd. 1. may not be used to exceed the maximum riser height under par. (b) or to decrease the minimum tread depth under par. (c).
SPS 321.04(2)(f)(f) Open risers. Stairways with open risers shall be constructed to prevent the through-passage of a sphere with a diameter of 4 inches or larger between any 2 adjacent treads.
SPS 321.04(2)(g)(g) Walking surface. The walking surface of stair treads and landings shall be a planar surface that is free of lips or protrusions that could present a tripping hazard.
SPS 321.04(3)(3)Handrails and guards.
SPS 321.04(3)(a)(a) General.
SPS 321.04(3)(a)1.1. A flight of stairs with more than 3 risers shall be provided with at least one handrail for the full length of the flight.
SPS 321.04(3)(a)2.2. Guards shall be provided on all open sides of stairs consisting of more than 3 risers and on all open sides of areas that are elevated more than 24 inches above the floor or exterior grade.
SPS 321.04 NoteNote: A handrail provided at 30 to 38 inches above the tread nosing meets the height requirement for a guard on a stairway.
SPS 321.04(3)(a)3.a.a. Except as provided in subd. 3. b., guards shall be constructed to prevent the through-passage of a sphere with a diameter of 4 3/8 inches, when applying a force of 4 pounds.
SPS 321.04(3)(a)3.b.b. The triangular area formed by the tread, riser and bottom rail shall have an opening size that prevents the through-passage of a sphere with a diameter of 6 inches, when applying a force of 4 pounds.
SPS 321.04(3)(a)3.c.c. Rope, cable, or similar materials used in guard infill shall be strung with maximum openings of 3 1/2 inches with vertical supports a maximum of 4 feet apart.
SPS 321.04 NoteNote: In some cases, the vertical supports could be simple cable stays that offer vertical support to the rope or cable span. Structural posts must be supplied to provide the rail with the minimum 200 pound load resistance, as well as to resist the tensile loads exerted by the tightened rope or cable.
SPS 321.04(3)(a)4.a.a. Handrails and guards shall be designed and constructed to withstand a 200 pound load applied in any direction.
SPS 321.04(3)(a)4.b.b. Handrail or guard infill components, balusters and panel fillers shall withstand a horizontally applied perpendicular load of 50 pounds on any one-foot-square area.